+44 (0) 151 909 2333

Multi-channel Power and Energy Meter

SATEC BFM136


SATEC BFM136 Branch Feeder Monitor For Multi-Circuit MeteringSATEC BFM136 Branch Feeder Monitor For Multi-Circuit Metering

The SATEC BFM136 Branch Feeder Monitor™ is a versatile multi-circuit power meter capable of monitoring up to 12 three-phase power circuits or 36 single-phase circuits, making it suitable for both new installations and retrofit projects.

Equipped with High Accuracy Current Sensors (HACS), the BFM136 is perfect for a variety of applications, ranging from medium-voltage substation monitoring to commercial multi-tenant billing in shopping centers and office buildings.

Cost-effective

  • Significantly reduces installation costs and minimizes space requirements compared to using multiple legacy meters

Multi-circuit modular options for multi-load metering

  • Up to 12 three-phase loads
  • Up to 36 single-phase loads
  • Various combinations of the two

Revenue Meter

  • Class 0.5S accuracy per IEC 62053-22
  • Tenant Billing & Monitoring
  • Time-Of-Use (TOU) Metering
  • Durable design for tamper resistance

Communication

  • Built-in ports: RS485; ETH
  • Protocols: Modbus, BACnet

Multi-option Current Inputs

  • 40mA for HACS CTs (100 - 3000A)
  • Special input: clip-on 5A HACS for retrofit
  • 100mA inputs for 3rd party CTs
Accuracy Class 0.5s Digital in/out Open Protocol BACnet Supported Cellular Connectivity

Description

The BFM136 monitors up to 12 three phase circuits, 18 two phase or 36 single phase circuits, or any combination of single, two or three phase circuits. This flexibility makes the BFM136 perfect for multi-tenant facilities such as residential projects, office buildings, data centers and shopping malls.

The compact BFM136 is designed to easily fit into existing panel boards or be flush mounted nearby, thus eliminating the need for expensive retrofit projects or for allocating extra space for the device.

The BFM136 monitors up to 36 currents via High Accuracy Current Sensors (HACS). Each HACS measures and reports the current consumed by each of the branch circuits at the panel board. For billing purposes, single or multiple circuits can be defined for each customer. This flexibility allows a simple reassignment of circuit groups without wiring changes, and allows for easy changes when tenants move in and out. Main panel board or load center installation makes for a valuable saving of both time and money.

The BFM136's user-defined and easily configured alarm system enables users to take predictive maintenance action in order to avoid unnecessary outages.

Billing & Time Of Use (TOU)

Tariffs vary according to different criteria, such as the week day, holiday, season or consumer type (private home accounts in multitenant buildings, businesses, industry etc.). The BFM136 provides data for TOU billing in compliance with the rates set by the local electricity supplier. Unlike some other meters on the market, the BFM136 stores the TOU information on its non-volatile memory, protecting the data in case of communication loss or power outage.

Applications

Energy Management Revenue Metering Substation Automation Data Center

Commercial Buildings

Many commercial buildings have a single electricity connection, while the building owner/manager is responsible for distributing the electricity to the tenants. Since charging the tenants based on floor area is no longer acceptable, an accurate, reliable and flexible system should be applied. The BFM136 is specially designed for such cases, allowing the owner/manager to easily monitor the consumption in a small footprint.

Using the BFM136 with SATEC Expertpower™ software will allow issuing invoices to the tenants based on real consumption.

Data Centers

Energy consumption of data centers is constantly rising, following the increase of computing performance. Monitoring the PUE (Power Usage Effectiveness—Total Facility Energy divided by the IT Equipment Energy) is essential. According to the US DoE (Department of Energy), data centers can achieve energy savings of 20-50% by utilizing today's best practices, including “continuously monitor energy” and “monitor energy at all levels.”

The practice of monitoring energy is becoming prevalent and modern data centers now include rack level monitoring at the design stage. The BFM136 monitors up to 36 single phase loads, which is ideal for this task, allowing for energy saving and offering high reliability.

SATEC BFM136 - Control Panel

Industrial Plants

Typically, industrial plants have many loads that are fed from the same MCC. It has been proven that online monitoring of the consumption down to a single load level results in energy saving of up to 30%.

The BFM136 is the most compact and efficient method to monitor several loads located up to 200m from the device, with uncomparable accuracy. The use of single device rather than separated meters makes it easy to install and maintain as well as single point for communication.

SATEC BFM136 - Features

Tech Specs

  • Power Meter

    • Power: voltage, current (including neutral current), power, energy (import & export), power factor, frequency, voltage/current unbalance
    • Ampere/Volt demand meter
    • Event and parameter data-logging
    • Measurement at 50/60 Hz
    • Sampling frequency: 64 samples per cycle
  • Revenue Meter

    • Class 0.5S / 0.5 accuracy per IEC 62053-22 / ANSI C12.20 for active energy
    • Class 1 accuracy for reactive energy
    • Bills up to 12 individual three-phase clients or 54 single-phase clients or various combinations in between
    • Time-of-Use billing and logging: 4 energy/demand registers x 6 tariffs, 4 seasons x 4 types of days, 8 tariff changes per day; easy programmable tariff schedule
  • Data Logger

    • Event recorder: non-volatile memory for timestamped event and data recording for each channel
    • Automatic 120-day daily profile for import/export energy and maximum demand readings (total and tariff registers) for each submeter
    • Logging internal diagnostic events and setup changes
    • 2 separate programmable data logs, on a periodic basis, per channel
    • 4 control setpoints, programmable thresholds and delays for each submeter
  • Variable Current Inputs

    36 current inputs, available in one of the following options:

    • 40mA HACS CT designated inputs (available HACS ratings: 100A-3,000A)
    • split-core HACS CTs for 5A secondary current
    • 100mA inputs for 3rd party CTs (not supplied by SATEC)
  • Voltage Measurement Inputs

    • Voltage measurement range: 120 (207) to 277 (480)V AC ± 15% (accuracy is guaranteed to this voltage range)
  • Display

    • Local LCD display providing up to 36 channels of consumption readings for each tenant
    • Optional RGM180 5.7” color touch screen
  • Communication Interfaces

    • RS-485
    • Optional 2nd port:
      • Ethernet 10/100Base-T
      • RF Modem
      • RS-232
      • RS-485 / RS-422
      • 2G/3G Cellular Modem
      • 56K Dial-up Modem
    • Communication Protocols

      • BACnet
      • Modbus
      • ASCII
    • Real Time Clock

      • Built-in clock and calendar functions
      • Accuracy: < 1 min/month @ 25°C
  • Power Supply

    • Self-Energized from measured voltage
    • Auto-range power supply: 88-552V AC
  • Meter Security

    • 3 level password security for protecting meter setups and accumulated data from unauthorized changes
    • Meter sealing option for voltage and current inputs
  • Mounting

    • DIN-rail
    • Wall mounting
  • Memory

    • 8MB Flash Memory for Data Logging

Downloads